Show on map
Gordonsville Energy LP — Power plant · Gas, combined cycle · Virginia Electric & Power Co
  • Combustion
  • Operating
  • 10 · 100 · 1,000 MW

Gordonsville Energy LP

Power plant · Gas, combined cycle

Key facts

Power plant · Gas, combined cycleran 53% of 2025 Operating
Capacity
Capacity: sourceEIA-860M · Open licenseMW
Commissioned
1994
Net generation, 2025
1,385,931 MWh
Grid
230 kV to Virginia Electric & Power Co (PJM)
Location
Louisa County, Virginia

Operations

Net generation, 2025
1,385,931MWh
Fuel burned, 2025
11,867,913MMBtu
Capacity factor, 2025
52.7%
Heat rate, 2025
8,563Btu/kWh
Capacity factor % of full output, by year
Heat rate Btu per kWh, by year
Net generation, fuel burned, capacity factor and heat rate by year, newest first, as EIA's bulk electricity file states them.
YearNet generation (MWh)Fuel burned (MMBtu)Capacity factorHeat rate (Btu/kWh)
20251,385,93111,867,91352.7%8,563
20241,386,87112,349,58852.6%8,905
2023918,0117,837,45634.9%8,537
20221,021,6548,695,55638.8%8,511
2021998,4198,268,39337.9%8,282
20201,173,4969,818,02444.5%8,366
20191,203,4889,898,53545.7%8,225
2018815,6526,748,00831.0%8,273
2017226,7271,943,7188.6%8,573
2016919,0457,503,59534.8%8,165
20151,150,0249,661,86143.7%8,401
2014630,9455,355,21524.0%8,488
2013917,9257,767,24934.9%8,462
20121,288,91710,913,87348.9%8,468
2011761,8466,474,71328.9%8,499
2010648,5905,426,36524.6%8,366
2009559,3994,774,33021.3%8,535
2008346,0982,950,74513.1%8,526
2007443,3973,636,62216.9%8,202
2006286,0062,396,86710.9%8,380
2005442,5093,743,53516.8%8,460
2004300,9682,586,12811.4%8,593
2003163,3441,272,9116.2%7,793
2002192,4151,678,3407.3%8,722
2001168,6091,593,1056.4%9,448
How these are worked out

Net generation and fuel burned are the monthly figures EIA publishes in its bulk electricity file, from the plant's Form 923 reports; a year is the sum of its months. Capacity factor is a full year's net generation over today's nameplate capacity times the hours in that year (8,784 in a leap year), so a plant uprated or partly retired since reads against its current size; heat rate is fuel burned over net generation, for plants that burn fuel. A year with fewer than twelve months stated has no capacity factor, and a value outside the plausible range is left blank rather than shown. By month, the charts apply the same rules to each month's own hours and fuel.

Sources

3 sources

Sources EIA-860M · GEM · EIA

Sources

  • EIA-860MOpen license · retrieved Nov 4, 2026
  • GEMOpen license, with credit · retrieved Oct 26, 2026Global Integrated Power Tracker, Global Energy Monitor, September 2026 release (https://globalenergymonitor.org/projects/global-integrated-power-tracker), CC BY 4.0. Modified by Inframation: TransitionZero-sourced rows removed; statuses and technologies mapped to Inframation's vocabulary; figures aggregated. Copyright © Global Energy Monitor. Global Integrated Power Tracker, September 2026 release. Distributed under a Creative Commons Attribution 4.0 International License.
  • EIAOpen license · retrieved Nov 1, 2026Source: U.S. Energy Information Administration, Electricity bulk data (Form EIA-923 monthly plant series)

Every source and license · Attribution

View at source