Show on map
Apache Station — Power plant · Gas, combustion turbine · Arizona Electric Pwr Coop Inc
  • Combustion
  • Operating
  • 10 · 100 · 1,000 MW

Apache Station

Power plant · Gas, combustion turbine

Key facts

Power plant · Gas, combustion turbineran 31% of 2025 Operating
Capacity
Capacity: sourceEIA-860M · Open licenseMW
Commissioned
1963
Net generation, 2025
2,156,520 MWh
Grid
230 kV, 115 kV, 69 kV to Arizona Electric Pwr Coop Inc (WALC)
Location
Cochise County, Arizona

Operations

Net generation, 2025
2,156,520MWh
Fuel burned, 2025
23,527,015MMBtu
Capacity factor, 2025
31.5%
Heat rate, 2025
10,910Btu/kWh
Capacity factor % of full output, by year
Heat rate Btu per kWh, by year
Net generation, fuel burned, capacity factor and heat rate by year, newest first, as EIA's bulk electricity file states them.
YearNet generation (MWh)Fuel burned (MMBtu)Capacity factorHeat rate (Btu/kWh)
2026 (8 of 12 months)1,350,64215,214,357—11,264
20252,156,52023,527,01531.5%10,910
20242,322,17925,666,87333.8%11,053
20231,982,37722,529,64928.9%11,365
20221,960,27821,709,88328.6%11,075
20211,995,50422,080,36629.1%11,065
20202,210,41424,565,31132.2%11,113
20192,002,81822,416,89329.2%11,193
20181,773,34320,130,04325.9%11,352
20171,704,00019,823,30424.9%11,633
20162,068,77923,126,86630.1%11,179
20151,959,04421,351,26428.6%10,899
20142,638,02728,191,89138.5%10,687
20132,327,13025,183,49934.0%10,822
20121,623,37418,062,20823.6%11,126
20111,959,14521,504,57028.6%10,976
20102,187,39623,966,76931.9%10,957
20092,099,28923,171,19330.7%11,038
20082,779,81529,723,16440.5%10,692
20073,061,39632,531,53144.7%10,626
20062,843,77330,087,54841.5%10,580
20052,876,04930,964,85042.0%10,766
20042,835,66930,352,82341.3%10,704
20032,961,61031,168,51143.2%10,524
20022,799,86129,471,68440.9%10,526
20013,186,35233,789,49746.5%10,604
How these are worked out

Net generation and fuel burned are the monthly figures EIA publishes in its bulk electricity file, from the plant's Form 923 reports; a year is the sum of its months. Capacity factor is a full year's net generation over today's nameplate capacity times the hours in that year (8,784 in a leap year), so a plant uprated or partly retired since reads against its current size; heat rate is fuel burned over net generation, for plants that burn fuel. A year with fewer than twelve months stated has no capacity factor, and a value outside the plausible range is left blank rather than shown. By month, the charts apply the same rules to each month's own hours and fuel.