Power plant · Gas, combustion turbine
Key facts
Power plant · Gas, combustion turbineran 5% of 2025 Operating- Capacity
- Capacity: sourceEIA-860M · Open licenseMW
- Commissioned
- 2001
- Net generation, 2025
- 498,735 MWh
- Grid
- 345 kV, 138 kV to Commonwealth Edison Co (PJM)
- Location
- DuPage County, Illinois
- Operated by
- Aurora Generation LLC
Operations
- Net generation, 2025
- 498,735
MWh - Fuel burned, 2025
- 5,330,425
MMBtu - Capacity factor, 2025
- 5.2
% - Heat rate, 2025
- 10,688
Btu/kWh
| Year | Net generation (MWh) | Fuel burned (MMBtu) | Capacity factor | Heat rate (Btu/kWh) |
|---|---|---|---|---|
| 2026 (8 of 12 months) | 298,274 | 3,316,202 | — | 11,118 |
| 2025 | 498,735 | 5,330,425 | 5.2% | 10,688 |
| 2024 | 354,861 | 3,864,933 | 3.7% | 10,891 |
| 2023 | 415,315 | 4,296,976 | 4.4% | 10,346 |
| 2022 | 339,135 | 3,564,744 | 3.6% | 10,511 |
| 2021 | 774,176 | 7,872,227 | 8.1% | 10,168 |
| 2020 | 768,846 | 7,653,464 | 8.1% | 9,954 |
| 2019 | 650,745 | 6,570,759 | 6.8% | 10,097 |
| 2018 | 677,827 | 7,096,667 | 7.1% | 10,470 |
| 2017 | 382,830 | 4,255,169 | 4.0% | 11,115 |
| 2016 | 382,098 | 4,160,973 | 4.0% | 10,890 |
| 2015 | 43,751 | 564,347 | 0.5% | 12,899 |
| 2014 | 49,707 | 614,889 | 0.5% | 12,370 |
| 2013 | 51,173 | 635,361 | 0.5% | 12,416 |
| 2012 | 74,785 | 879,609 | 0.8% | 11,762 |
| 2011 | 53,041 | 609,518 | 0.6% | 11,492 |
| 2010 | 31,799 | 340,558 | 0.3% | 10,710 |
| 2009 | 15,074 | 158,544 | 0.2% | 10,518 |
| 2008 | 64,898 | 672,974 | 0.7% | 10,370 |
| 2007 | 186,401 | 1,981,750 | 2.0% | 10,632 |
| 2006 | 88,984 | 925,701 | 0.9% | 10,403 |
| 2005 | 307,708 | 3,246,866 | 3.2% | 10,552 |
| 2004 | 53,134 | 551,250 | 0.6% | 10,375 |
| 2003 | 81,123 | 862,524 | 0.9% | 10,632 |
| 2002 | 218,563 | 2,290,972 | 2.3% | 10,482 |
| 2001 (9 of 12 months) | 162,809 | 1,729,236 | — | 10,621 |
How these are worked out
Net generation and fuel burned are the monthly figures EIA publishes in its bulk electricity file, from the plant's Form 923 reports; a year is the sum of its months. Capacity factor is a full year's net generation over today's nameplate capacity times the hours in that year (8,784 in a leap year), so a plant uprated or partly retired since reads against its current size; heat rate is fuel burned over net generation, for plants that burn fuel. A year with fewer than twelve months stated has no capacity factor, and a value outside the plausible range is left blank rather than shown. By month, the charts apply the same rules to each month's own hours and fuel.
Sources
3 sourcesSources
- EIA-860M
- GEMGlobal Integrated Power Tracker, Global Energy Monitor, September 2026 release (https://globalenergymonitor.org/projects/global-integrated-power-tracker), CC BY 4.0. Modified by Inframation: TransitionZero-sourced rows removed; statuses and technologies mapped to Inframation's vocabulary; figures aggregated. Copyright © Global Energy Monitor. Global Integrated Power Tracker, September 2026 release. Distributed under a Creative Commons Attribution 4.0 International License.
- EIASource: U.S. Energy Information Administration, Electricity bulk data (Form EIA-923 monthly plant series)