- Combustion
- Operating
- 10 · 100 · 1,000 MW
Map
- Combustion
- Operating
Campbell Industrial Park: location. Basemap: Protomaps, © OpenStreetMap contributors, ODbL.
Campbell Industrial Park
Power plant · Oil
Key facts
Power plant · Oilran 9% of 2025 Operating- Capacity
- Capacity: sourceEIA-860M · Open licenseMW
- Commissioned
- 2009
- Net generation, 2025
- 93,553 MWh
- Grid
- 12 kV to Hawaiian Electric Co Inc
- Location
- Honolulu County, Hawaii
- Operated by
- Hawaiian Electric Co Inc
Operations
- Net generation, 2025
- 93,553
MWh - Fuel burned, 2025
- 1,611,865
MMBtu - Capacity factor, 2025
- 9.4
% - Heat rate, 2025
- 17,229
Btu/kWh
| Year | Net generation (MWh) | Fuel burned (MMBtu) | Capacity factor | Heat rate (Btu/kWh) |
|---|---|---|---|---|
| 2026 (8 of 12 months) | 95,520 | 1,509,756 | — | 15,806 |
| 2025 | 93,553 | 1,611,865 | 9.4% | 17,229 |
| 2024 | 95,005 | 1,498,567 | 9.6% | 15,774 |
| 2023 | 126,338 | 2,161,873 | 12.8% | 17,112 |
| 2022 | 102,544 | 1,689,212 | 10.4% | 16,473 |
| 2021 | 95,062 | 1,590,490 | 9.6% | 16,731 |
| 2020 | 83,712 | 1,410,821 | 8.4% | 16,853 |
| 2019 | 99,232 | 1,703,597 | 10.0% | 17,168 |
| 2018 | 34,207 | 585,220 | 3.5% | 17,108 |
| 2017 | 54,323 | 895,087 | 5.5% | 16,477 |
| 2016 | 37,490 | 632,867 | 3.8% | 16,881 |
| 2015 | 52,424 | 852,674 | 5.3% | 16,265 |
| 2014 | 36,573 | 609,411 | 3.7% | 16,663 |
| 2013 | 28,507 | 519,350 | 2.9% | 18,218 |
| 2012 | 21,613 | 402,578 | 2.2% | 18,627 |
| 2011 | 24,203 | 438,293 | 2.5% | 18,109 |
| 2010 | 10,978 | 218,628 | 1.1% | 19,915 |
| 2009 (6 of 12 months) | 24,196 | 350,520 | — | 14,487 |
How these are worked out
Net generation and fuel burned are the monthly figures EIA publishes in its bulk electricity file, from the plant's Form 923 reports; a year is the sum of its months. Capacity factor is a full year's net generation over today's nameplate capacity times the hours in that year (8,784 in a leap year), so a plant uprated or partly retired since reads against its current size; heat rate is fuel burned over net generation, for plants that burn fuel. A year with fewer than twelve months stated has no capacity factor, and a value outside the plausible range is left blank rather than shown. By month, the charts apply the same rules to each month's own hours and fuel.
Sources
3 sourcesSources
- EIA-860M
- GEMGlobal Integrated Power Tracker, Global Energy Monitor, September 2026 release (https://globalenergymonitor.org/projects/global-integrated-power-tracker), CC BY 4.0. Modified by Inframation: TransitionZero-sourced rows removed; statuses and technologies mapped to Inframation's vocabulary; figures aggregated. Copyright © Global Energy Monitor. Global Integrated Power Tracker, September 2026 release. Distributed under a Creative Commons Attribution 4.0 International License.
- EIASource: U.S. Energy Information Administration, Electricity bulk data (Form EIA-923 monthly plant series)