- Combustion
- Retired
- 10 · 100 · 1,000 MW
Map
- Combustion
- Retired
Great Lakes Central Power Plant: location. Basemap: Protomaps, © OpenStreetMap contributors, ODbL.
Great Lakes Central Power Plant
Power plant · Gas, combustion turbine
Key facts
Power plant · Gas, combustion turbineran 29% of 2014 Retired- Capacity
- Capacity: sourceEIA-860M · Open licenseMW
- Commissioned
- 1998
- Net generation, 2014
- 35,986 MWh
- Location
- Lake County, Illinois
- Operated by
- NAVFAC Midlant PWD Great LakesSourceEIA-860M Preliminary Monthly Electric Generator Inventory
Operations
- Net generation, 2014
- 35,986
MWh - Fuel burned, 2014
- 828,862
MMBtu - Capacity factor, 2014
- 29.3
% - Heat rate, 2014
- 23,033
Btu/kWh
| Year | Net generation (MWh) | Fuel burned (MMBtu) | Capacity factor | Heat rate (Btu/kWh) |
|---|---|---|---|---|
| 2015 (9 of 12 months) | 18,045 | 350,734 | — | 19,437 |
| 2014 | 35,986 | 828,862 | 29.3% | 23,033 |
How these are worked out
Net generation and fuel burned are the monthly figures EIA publishes in its bulk electricity file, from the plant's Form 923 reports; a year is the sum of its months. Capacity factor is a full year's net generation over today's nameplate capacity times the hours in that year (8,784 in a leap year), so a plant uprated or partly retired since reads against its current size; heat rate is fuel burned over net generation, for plants that burn fuel. A year with fewer than twelve months stated has no capacity factor, and a value outside the plausible range is left blank rather than shown. By month, the charts apply the same rules to each month's own hours and fuel.