Show on map
Hanford Energy Park Peaker — Power plant · Gas, combustion turbine · MRP San Joaquin Energy LLC.
  • Combustion
  • Operating
  • 10 · 100 · 1,000 MW

Hanford Energy Park Peaker

Power plant · Gas, combustion turbine

Key facts

Power plant · Gas, combustion turbineran 0% of 2025 Operating
Capacity
Capacity: sourceEIA-860M · Open licenseMW
Commissioned
2001
Net generation, 2025
2,981 MWh
Grid
115 kV to Pacific Gas & Electric Co (CISO)
Location
Kings County, California

Operations

Net generation, 2025
2,981MWh
Fuel burned, 2025
39,589MMBtu
Capacity factor, 2025
0.4%
Heat rate, 2025
13,280Btu/kWh
Capacity factor % of full output, by year
Heat rate Btu per kWh, by year
Net generation, fuel burned, capacity factor and heat rate by year, newest first, as EIA's bulk electricity file states them.
YearNet generation (MWh)Fuel burned (MMBtu)Capacity factorHeat rate (Btu/kWh)
2026 (8 of 12 months)1,84919,872—10,747
20252,98139,5890.4%13,280
20247,26480,1120.9%11,029
20234,05045,7810.5%11,304
202218,850211,6252.3%11,227
20218,33793,0571.0%11,162
202018,540220,5732.3%11,897
201910,679129,8741.3%12,162
201815,605183,1001.9%11,733
201719,577226,2442.4%11,557
201625,634293,9883.2%11,469
201598,3501,070,58912.2%10,886
2014162,2261,732,40620.1%10,679
2013124,2251,363,26615.4%10,974
201276,684856,1279.5%11,164
201110,733120,3881.3%11,217
201019,297212,9812.4%11,037
200960,697643,6747.5%10,605
200845,538465,0215.6%10,212
200735,714396,3134.4%11,097
200621,084215,0492.6%10,200
200531,875339,2514.0%10,643
20049,65497,5551.2%10,105
200317,774184,5592.2%10,384
200239,435402,2014.9%10,199
2001 (4 of 12 months)25,525251,877—9,868
How these are worked out

Net generation and fuel burned are the monthly figures EIA publishes in its bulk electricity file, from the plant's Form 923 reports; a year is the sum of its months. Capacity factor is a full year's net generation over today's nameplate capacity times the hours in that year (8,784 in a leap year), so a plant uprated or partly retired since reads against its current size; heat rate is fuel burned over net generation, for plants that burn fuel. A year with fewer than twelve months stated has no capacity factor, and a value outside the plausible range is left blank rather than shown. By month, the charts apply the same rules to each month's own hours and fuel.

Sources

3 sources

Sources EIA-860M · GEM · EIA

Sources

  • EIA-860MOpen license · retrieved Nov 4, 2026
  • GEMOpen license, with credit · retrieved Oct 26, 2026Global Integrated Power Tracker, Global Energy Monitor, September 2026 release (https://globalenergymonitor.org/projects/global-integrated-power-tracker), CC BY 4.0. Modified by Inframation: TransitionZero-sourced rows removed; statuses and technologies mapped to Inframation's vocabulary; figures aggregated. Copyright © Global Energy Monitor. Global Integrated Power Tracker, September 2026 release. Distributed under a Creative Commons Attribution 4.0 International License.
  • EIAOpen license · retrieved Nov 1, 2026Source: U.S. Energy Information Administration, Electricity bulk data (Form EIA-923 monthly plant series)

Every source and license · Attribution

View at source