Show on map
Jasper — Power plant · Gas, combined cycle · Dominion Energy South Carolina, Inc
  • Combustion
  • Operating
  • 10 · 100 · 1,000 MW

Power plant · Gas, combined cycle

Key facts

Power plant · Gas, combined cycleran 39% of 2025 Operating
Capacity
Capacity: sourceEIA-860M · Open licenseMW
Commissioned
2004
Net generation, 2025
3,603,980 MWh
Grid
230 kV to Dominion Energy South Carolina (SCEG)
Location
Jasper County, South Carolina

Operations

Net generation, 2025
3,603,980MWh
Fuel burned, 2025
25,991,554MMBtu
Capacity factor, 2025
38.5%
Heat rate, 2025
7,212Btu/kWh
Capacity factor % of full output, by year
Heat rate Btu per kWh, by year
Net generation, fuel burned, capacity factor and heat rate by year, newest first, as EIA's bulk electricity file states them.
YearNet generation (MWh)Fuel burned (MMBtu)Capacity factorHeat rate (Btu/kWh)
2026 (8 of 12 months)3,052,17422,033,650—7,219
20253,603,98025,991,55438.5%7,212
20244,613,68133,643,53449.2%7,292
20235,318,40238,703,19856.8%7,277
20225,083,53837,470,50154.3%7,371
20214,742,81935,393,35550.7%7,462
20205,254,91638,924,71956.0%7,407
20195,184,18638,353,45755.4%7,398
20185,061,07237,300,02854.1%7,370
20175,482,93140,743,56758.6%7,431
20164,784,26035,672,55851.0%7,456
20155,500,60440,847,96258.8%7,426
20144,243,52831,173,76545.4%7,346
20134,695,52834,415,23450.2%7,329
20124,815,44135,208,29351.3%7,312
20115,549,56440,766,14559.3%7,346
20104,342,60131,977,55746.4%7,364
20094,279,73731,493,21445.7%7,359
20082,409,52318,073,76225.7%7,501
20072,189,41516,406,56923.4%7,494
20061,783,26813,376,21619.1%7,501
20051,666,94412,692,15417.8%7,614
2004 (5 of 12 months)493,0083,747,251—7,601
How these are worked out

Net generation and fuel burned are the monthly figures EIA publishes in its bulk electricity file, from the plant's Form 923 reports; a year is the sum of its months. Capacity factor is a full year's net generation over today's nameplate capacity times the hours in that year (8,784 in a leap year), so a plant uprated or partly retired since reads against its current size; heat rate is fuel burned over net generation, for plants that burn fuel. A year with fewer than twelve months stated has no capacity factor, and a value outside the plausible range is left blank rather than shown. By month, the charts apply the same rules to each month's own hours and fuel.

Sources

3 sources

Sources EIA-860M · GEM · EIA

Sources

  • EIA-860MOpen license · retrieved Nov 4, 2026
  • GEMOpen license, with credit · retrieved Oct 26, 2026Global Integrated Power Tracker, Global Energy Monitor, September 2026 release (https://globalenergymonitor.org/projects/global-integrated-power-tracker), CC BY 4.0. Modified by Inframation: TransitionZero-sourced rows removed; statuses and technologies mapped to Inframation's vocabulary; figures aggregated. Copyright © Global Energy Monitor. Global Integrated Power Tracker, September 2026 release. Distributed under a Creative Commons Attribution 4.0 International License.
  • EIAOpen license · retrieved Nov 1, 2026Source: U.S. Energy Information Administration, Electricity bulk data (Form EIA-923 monthly plant series)

Every source and license · Attribution

View at source