Show on map
King & Queen — Power plant · Biomass · Industrial Power Generating Company LLC
  • Bioenergy
  • Operating
  • 10 · 100 · 1,000 MW

King & Queen

Power plant · Biomass

Key facts

Power plant · Biomassran 69% of 2025 Operating
Capacity
Capacity: sourceEIA-860M · Open licenseMW
Commissioned
2008
Net generation, 2025
64,957 MWh
Grid
34 kV to Virginia Electric & Power Co (PJM)
Location
King and Queen County, Virginia
Operated by
Industrial Power Generating Company LLCSourceEIA-860M Preliminary Monthly Electric Generator Inventory

Operations

Net generation, 2025
64,957MWh
Fuel burned, 2025
644,033MMBtu
Capacity factor, 2025
68.7%
Heat rate, 2025
9,915Btu/kWh
Capacity factor % of full output, by year
Heat rate Btu per kWh, by year
Net generation, fuel burned, capacity factor and heat rate by year, newest first, as EIA's bulk electricity file states them.
YearNet generation (MWh)Fuel burned (MMBtu)Capacity factorHeat rate (Btu/kWh)
202564,957644,03368.7%9,915
202459,909617,37763.1%10,305
202353,765584,54556.8%10,872
202261,527675,69965.0%10,982
202159,684708,41363.1%11,869
202058,797685,04762.0%11,651
201960,592657,63964.0%10,854
201867,312674,42071.2%10,019
201764,400644,37668.1%10,006
201661,789724,49765.1%11,725
201563,909749,96167.5%11,735
201464,128702,86467.8%10,960
201334,692403,39936.7%11,628
201236,880381,29338.9%10,339
20115,28252,0925.6%9,862
201024,661279,18026.1%11,321
200916,201152,05617.1%9,386
200831,245247,12232.9%7,909
How these are worked out

Net generation and fuel burned are the monthly figures EIA publishes in its bulk electricity file, from the plant's Form 923 reports; a year is the sum of its months. Capacity factor is a full year's net generation over today's nameplate capacity times the hours in that year (8,784 in a leap year), so a plant uprated or partly retired since reads against its current size; heat rate is fuel burned over net generation, for plants that burn fuel. A year with fewer than twelve months stated has no capacity factor, and a value outside the plausible range is left blank rather than shown. By month, the charts apply the same rules to each month's own hours and fuel.

Sources

2 sources

Sources EIA-860M · EIA

Sources

  • EIA-860MOpen license · retrieved Nov 4, 2026
  • EIAOpen license · retrieved Nov 1, 2026Source: U.S. Energy Information Administration, Electricity bulk data (Form EIA-923 monthly plant series)

Every source and license · Attribution

View at source