Show on map
Lon Wright — Power plant · Coal · City of Fremont - (NE)
  • Combustion
  • Operating
  • 10 · 100 · 1,000 MW

Power plant · Coal

Key facts

Power plant · Coalran 31% of 2025 Operating
Capacity
Capacity: sourceEIA-860M · Open licenseMW
Commissioned
1957
Net generation, 2025
465,819 MWh
Grid
69 kV to City of Fremont - (NE) (SWPP)
Location
Dodge County, Nebraska

Operations

Net generation, 2025
465,819MWh
Fuel burned, 2025
5,614,405MMBtu
Capacity factor, 2025
30.9%
Heat rate, 2025
12,053Btu/kWh
Capacity factor % of full output, by year
Heat rate Btu per kWh, by year
Net generation, fuel burned, capacity factor and heat rate by year, newest first, as EIA's bulk electricity file states them.
YearNet generation (MWh)Fuel burned (MMBtu)Capacity factorHeat rate (Btu/kWh)
2025465,8195,614,40530.9%12,053
2024515,6696,210,47134.1%12,044
2023521,5796,209,06034.6%11,904
2022447,8245,349,01429.7%11,944
2021490,7375,762,53332.5%11,743
2020603,7066,723,33239.9%11,137
2019649,1057,236,35143.0%11,148
2018479,0485,840,49931.7%12,192
2017455,0695,548,59330.1%12,193
2016457,7735,665,37430.2%12,376
2015429,3335,495,80328.4%12,801
2014473,8675,806,79131.4%12,254
2013481,8125,991,16131.9%12,435
2012454,3285,552,53430.0%12,221
2011455,8125,507,35230.2%12,082
2010467,2805,605,02431.0%11,995
2009340,2634,952,44322.5%14,555
2008554,7326,504,71736.6%11,726
2007561,8986,714,64737.2%11,950
2006563,6056,682,65237.3%11,857
2005551,8106,761,25236.6%12,253
2004494,8845,981,24932.7%12,086
2003441,2395,116,70829.2%11,596
2002438,4065,027,49829.0%11,468
2001403,6494,846,17526.7%12,006
How these are worked out

Net generation and fuel burned are the monthly figures EIA publishes in its bulk electricity file, from the plant's Form 923 reports; a year is the sum of its months. Capacity factor is a full year's net generation over today's nameplate capacity times the hours in that year (8,784 in a leap year), so a plant uprated or partly retired since reads against its current size; heat rate is fuel burned over net generation, for plants that burn fuel. A year with fewer than twelve months stated has no capacity factor, and a value outside the plausible range is left blank rather than shown. By month, the charts apply the same rules to each month's own hours and fuel.

Sources

3 sources

Sources EIA-860M · GEM · EIA

Sources

Every source and license · Attribution

View at source