Show on map
Rex Brown — Power plant · Gas, steam turbine · Entergy Mississippi LLC
  • Combustion
  • Retired
  • 10 · 100 · 1,000 MW

Power plant · Gas, steam turbine

Key facts

Power plant · Gas, steam turbineran 3% of 2019 Retired
Capacity
Capacity: sourceEIA-860M · Open licenseMW
Commissioned
1948
Net generation, 2019
84,455 MWh
Grid
115 kV to Entergy Mississippi Inc (MISO)
Location
Hinds County, Mississippi

Operations

Net generation, 2019
84,455MWh
Fuel burned, 2019
1,154,887MMBtu
Capacity factor, 2019
2.8%
Heat rate, 2019
13,675Btu/kWh
Capacity factor % of full output, by year
Heat rate Btu per kWh, by year
Net generation, fuel burned, capacity factor and heat rate by year, newest first, as EIA's bulk electricity file states them.
YearNet generation (MWh)Fuel burned (MMBtu)Capacity factorHeat rate (Btu/kWh)
201984,4551,154,8872.8%13,675
2018158,2212,046,1605.2%12,932
2017166,7462,044,9105.5%12,264
2016277,4803,294,3389.0%11,872
201511,698165,1680.4%14,119
201463,678900,9332.1%14,148
201377,8411,425,5672.5%18,314
2012161,1342,527,3415.2%15,685
2011177,2622,764,9565.8%15,598
2010132,0852,061,9924.3%15,611
200972,4131,209,3262.4%16,700
200894,7241,461,6133.1%15,430
2007159,4812,524,8995.2%15,832
2006156,5162,366,3145.1%15,119
2005206,9592,949,0176.8%14,249
2004205,7963,059,1166.7%14,865
2003 (11 of 12 months)218,9953,134,339—14,312
2002424,6145,790,82713.9%13,638
2001473,3896,374,49815.5%13,466
How these are worked out

Net generation and fuel burned are the monthly figures EIA publishes in its bulk electricity file, from the plant's Form 923 reports; a year is the sum of its months. Capacity factor is a full year's net generation over today's nameplate capacity times the hours in that year (8,784 in a leap year), so a plant uprated or partly retired since reads against its current size; heat rate is fuel burned over net generation, for plants that burn fuel. A year with fewer than twelve months stated has no capacity factor, and a value outside the plausible range is left blank rather than shown. By month, the charts apply the same rules to each month's own hours and fuel.

Sources

2 sources

Sources EIA-860M · EIA

Sources

  • EIA-860MOpen license · retrieved Nov 4, 2026
  • EIAOpen license · retrieved Nov 1, 2026Source: U.S. Energy Information Administration, Electricity bulk data (Form EIA-923 monthly plant series)

Every source and license · Attribution

View at source