- Combustion
- Operating
- 10 · 100 · 1,000 MW
Map
- Combustion
- Operating
South Point Energy Center: location. Basemap: Protomaps, © OpenStreetMap contributors, ODbL.
South Point Energy Center
Power plant · Gas, combined cycle
Key facts
Power plant · Gas, combined cycleran 33% of 2025 Operating- Capacity
- Capacity: sourceEIA-860M · Open licenseMW
- Commissioned
- 2001
- Net generation, 2025
- 2,024,909 MWh
- Grid
- 230 kV to WAPA-- Western Area Power Administration (WALC)
- Location
- Mohave County, Arizona
- Operated by
- South Point Energy Center LLC
Operations
- Net generation, 2025
- 2,024,909
MWh - Fuel burned, 2025
- 15,252,003
MMBtu - Capacity factor, 2025
- 32.6
% - Heat rate, 2025
- 7,532
Btu/kWh
| Year | Net generation (MWh) | Fuel burned (MMBtu) | Capacity factor | Heat rate (Btu/kWh) |
|---|---|---|---|---|
| 2026 (8 of 12 months) | 1,923,451 | 14,091,651 | — | 7,326 |
| 2025 | 2,024,909 | 15,252,003 | 32.6% | 7,532 |
| 2024 | 2,686,489 | 21,680,259 | 43.2% | 8,070 |
| 2023 | 2,671,767 | 21,463,684 | 43.1% | 8,034 |
| 2022 | 1,675,601 | 13,648,392 | 27.0% | 8,145 |
| 2021 | 2,744,912 | 21,941,744 | 44.3% | 7,994 |
| 2020 | 3,058,293 | 24,499,073 | 49.2% | 8,011 |
| 2019 | 1,886,216 | 14,991,211 | 30.4% | 7,948 |
| 2018 | 261,151 | 2,132,875 | 4.2% | 8,167 |
| 2017 | 0 | 0 | — | — |
| 2016 | 100,404 | 812,020 | 1.6% | 8,088 |
| 2015 | 1,750,652 | 13,745,850 | 28.2% | 7,852 |
| 2014 | 1,106,812 | 8,895,944 | 17.8% | 8,037 |
| 2013 | 1,934,275 | 15,447,576 | 31.2% | 7,986 |
| 2012 | 1,360,093 | 10,038,310 | 21.9% | 7,381 |
| 2011 | 805,648 | 6,195,684 | 13.0% | 7,690 |
| 2010 | 1,762,385 | 13,191,319 | 28.4% | 7,485 |
| 2009 | 2,075,439 | 15,211,184 | 33.5% | 7,329 |
| 2008 | 2,717,158 | 19,803,308 | 43.7% | 7,288 |
| 2007 | 2,115,788 | 15,650,559 | 34.1% | 7,397 |
| 2006 | 2,400,459 | 17,968,563 | 38.7% | 7,486 |
| 2005 | 1,481,357 | 11,140,391 | 23.9% | 7,520 |
| 2004 | 2,909,039 | 20,708,832 | 46.8% | 7,119 |
| 2003 | 2,893,496 | 20,887,156 | 46.7% | 7,219 |
| 2002 | 3,331,352 | 23,380,370 | 53.7% | 7,018 |
| 2001 (8 of 12 months) | 2,080,055 | 14,324,571 | — | 6,887 |
How these are worked out
Net generation and fuel burned are the monthly figures EIA publishes in its bulk electricity file, from the plant's Form 923 reports; a year is the sum of its months. Capacity factor is a full year's net generation over today's nameplate capacity times the hours in that year (8,784 in a leap year), so a plant uprated or partly retired since reads against its current size; heat rate is fuel burned over net generation, for plants that burn fuel. A year with fewer than twelve months stated has no capacity factor, and a value outside the plausible range is left blank rather than shown. By month, the charts apply the same rules to each month's own hours and fuel.
Sources
3 sourcesSources
- EIA-860M
- GEMGlobal Integrated Power Tracker, Global Energy Monitor, September 2026 release (https://globalenergymonitor.org/projects/global-integrated-power-tracker), CC BY 4.0. Modified by Inframation: TransitionZero-sourced rows removed; statuses and technologies mapped to Inframation's vocabulary; figures aggregated. Copyright © Global Energy Monitor. Global Integrated Power Tracker, September 2026 release. Distributed under a Creative Commons Attribution 4.0 International License.
- EIASource: U.S. Energy Information Administration, Electricity bulk data (Form EIA-923 monthly plant series)