- Bioenergy
- Operating
- 10 · 100 · 1,000 MW
Map
- Bioenergy
- Operating
Tazewell Gas Recovery: location. Basemap: Protomaps, © OpenStreetMap contributors, ODbL.
Tazewell Gas Recovery
Power plant · Biomass
Key facts
Power plant · Biomassran 51% of 2025 Operating- Capacity
- Capacity: sourceEIA-860M · Open licenseMW
- Commissioned
- 1989
- Net generation, 2025
- 10,720 MWh
- Grid
- 13 kV to Ameren Illinois Company (MISO)
- Location
- Tazewell County, Illinois
- Operated by
- WM Illinois Renewable Energy LLC
Operations
- Net generation, 2025
- 10,720
MWh - Fuel burned, 2025
- 147,120
MMBtu - Capacity factor, 2025
- 51.0
% - Heat rate, 2025
- 13,724
Btu/kWh
| Year | Net generation (MWh) | Fuel burned (MMBtu) | Capacity factor | Heat rate (Btu/kWh) |
|---|---|---|---|---|
| 2025 | 10,720 | 147,120 | 51.0% | 13,724 |
| 2024 | 13,452 | 171,277 | 63.8% | 12,732 |
| 2023 | 14,167 | 178,142 | 67.4% | 12,574 |
| 2022 | 15,062 | 189,922 | 71.6% | 12,609 |
| 2021 | 15,994 | 203,366 | 76.1% | 12,715 |
| 2020 | 17,301 | 216,439 | 82.1% | 12,510 |
| 2019 | 16,684 | 204,268 | 79.4% | 12,243 |
| 2018 | 17,077 | 211,456 | 81.2% | 12,382 |
| 2017 | 16,725 | 223,398 | 79.5% | 13,357 |
| 2016 | 18,464 | 227,059 | 87.6% | 12,297 |
| 2015 | 18,438 | 228,563 | 87.7% | 12,396 |
| 2014 | 18,343 | 223,787 | 87.2% | 12,200 |
| 2013 | 18,465 | 224,885 | 87.8% | 12,179 |
| 2012 | 18,492 | 221,375 | 87.7% | 11,971 |
| 2011 | 17,005 | 210,614 | 80.9% | 12,385 |
| 2010 | 16,662 | 209,065 | 79.2% | 12,547 |
| 2009 | 17,940 | 220,188 | 85.3% | 12,274 |
| 2008 | 18,419 | 226,289 | 87.4% | 12,286 |
| 2007 | 18,744 | 227,329 | 89.2% | 12,128 |
| 2006 | 17,419 | 199,830 | 82.8% | 11,472 |
| 2005 | 16,561 | 199,599 | 78.8% | 12,052 |
| 2004 | 18,073 | 214,632 | 85.7% | 11,876 |
| 2003 | 17,905 | 211,019 | 85.2% | 11,786 |
| 2002 | 17,472 | 229,955 | 83.1% | 13,161 |
| 2001 | 17,950 | 211,963 | 85.4% | 11,808 |
How these are worked out
Net generation and fuel burned are the monthly figures EIA publishes in its bulk electricity file, from the plant's Form 923 reports; a year is the sum of its months. Capacity factor is a full year's net generation over today's nameplate capacity times the hours in that year (8,784 in a leap year), so a plant uprated or partly retired since reads against its current size; heat rate is fuel burned over net generation, for plants that burn fuel. A year with fewer than twelve months stated has no capacity factor, and a value outside the plausible range is left blank rather than shown. By month, the charts apply the same rules to each month's own hours and fuel.