- Combustion
- Operating
- 10 · 100 · 1,000 MW
Map
- Combustion
- Operating
TES Filer City Station: location. Basemap: Protomaps, © OpenStreetMap contributors, ODbL.
TES Filer City Station
Power plant · Coal
Key facts
Power plant · Coalran 57% of 2025 Operating- Capacity
- Capacity: sourceEIA-860M · Open licenseMW
- Commissioned
- 1990
- Net generation, 2025
- 351,278 MWh
- Grid
- 138 kV to ITC Transmission (MISO)
- Location
- Manistee County, Michigan
- Operated by
- TES Filer City Station LP
Operations
- Net generation, 2025
- 351,278
MWh - Fuel burned, 2025
- 4,609,006
MMBtu - Capacity factor, 2025
- 57.3
% - Heat rate, 2025
- 13,121
Btu/kWh
| Year | Net generation (MWh) | Fuel burned (MMBtu) | Capacity factor | Heat rate (Btu/kWh) |
|---|---|---|---|---|
| 2026 (8 of 12 months) | 172,854 | 2,465,850 | — | 14,266 |
| 2025 | 351,278 | 4,609,006 | 57.3% | 13,121 |
| 2024 | 230,199 | 3,171,621 | 37.4% | 13,778 |
| 2023 | 317,740 | 4,074,143 | 51.8% | 12,822 |
| 2022 | 498,457 | 6,038,196 | 81.3% | 12,114 |
| 2021 | 488,833 | 6,270,476 | 79.7% | 12,827 |
| 2020 | 510,430 | 6,491,593 | 83.0% | 12,718 |
| 2019 | 452,985 | 5,716,309 | 73.9% | 12,619 |
| 2018 | 505,400 | 6,474,114 | 82.4% | 12,810 |
| 2017 | 486,901 | 6,463,238 | 79.4% | 13,274 |
| 2016 | 506,326 | 6,492,353 | 82.3% | 12,822 |
| 2015 | 505,019 | 6,665,611 | 82.4% | 13,199 |
| 2014 | 497,734 | 6,705,675 | 81.2% | 13,472 |
| 2013 | 454,367 | 6,446,578 | 74.1% | 14,188 |
| 2012 | 492,294 | 6,724,109 | 80.1% | 13,659 |
| 2011 | 454,695 | 6,282,651 | 74.2% | 13,817 |
| 2010 | 493,743 | 6,783,993 | 80.5% | 13,740 |
| 2009 | 501,694 | 6,736,698 | 81.8% | 13,428 |
| 2008 | 482,382 | 6,487,563 | 78.5% | 13,449 |
| 2007 | 484,115 | 6,579,089 | 79.0% | 13,590 |
| 2006 | 490,179 | 6,610,303 | 79.9% | 13,486 |
| 2005 | 448,582 | 5,764,326 | 73.2% | 12,850 |
| 2004 | 497,585 | 6,368,710 | 80.9% | 12,799 |
| 2003 | 458,857 | 6,101,760 | 74.8% | 13,298 |
| 2002 | 268,902 | 3,506,511 | 43.9% | 13,040 |
| 2001 | 433,103 | 5,414,375 | 70.6% | 12,501 |
How these are worked out
Net generation and fuel burned are the monthly figures EIA publishes in its bulk electricity file, from the plant's Form 923 reports; a year is the sum of its months. Capacity factor is a full year's net generation over today's nameplate capacity times the hours in that year (8,784 in a leap year), so a plant uprated or partly retired since reads against its current size; heat rate is fuel burned over net generation, for plants that burn fuel. A year with fewer than twelve months stated has no capacity factor, and a value outside the plausible range is left blank rather than shown. By month, the charts apply the same rules to each month's own hours and fuel.