Show on map
Dallman — Power plant · Coal · City of Springfield - (IL)
  • Combustion
  • Operating
  • 10 · 100 · 1,000 MW

Power plant · Coal

Key facts

Power plant · Coalran 45% of 2025 Operating
Capacity
Capacity: sourceEIA-860M · Open licenseMW
Commissioned
2009
Net generation, 2025
900,919 MWh
Grid
138 kV, 69 kV to City of Springfield - (IL) (MISO)
Location
Sangamon County, Illinois

Operations

Net generation, 2025
900,919MWh
Fuel burned, 2025
10,470,563MMBtu
Capacity factor, 2025
44.7%
Heat rate, 2025
11,622Btu/kWh
Capacity factor % of full output, by year
Heat rate Btu per kWh, by year
Net generation, fuel burned, capacity factor and heat rate by year, newest first, as EIA's bulk electricity file states them.
YearNet generation (MWh)Fuel burned (MMBtu)Capacity factorHeat rate (Btu/kWh)
2026 (8 of 12 months)507,1975,909,317—11,651
2025900,91910,470,56344.7%11,622
2024547,2106,773,97127.1%12,379
2023643,1327,751,34131.9%12,052
20221,250,27813,236,14062.0%10,587
20211,225,02413,572,11960.8%11,079
2020755,9219,065,36637.4%11,992
20191,853,88921,772,41392.0%11,744
20182,355,82927,381,951—11,623
20172,388,18527,099,790—11,347
20161,785,39621,170,26988.3%11,858
20151,928,62722,295,20495.7%11,560
20142,346,72126,285,951—11,201
20132,378,30426,671,408—11,214
20121,953,68422,998,00596.7%11,772
20112,267,39425,975,853—11,456
20102,551,99829,424,098—11,530
20091,835,61521,971,66891.1%11,970
20081,439,18515,538,63071.2%10,797
20071,759,57720,465,60187.3%11,631
20061,782,54020,919,31188.4%11,736
20052,084,10423,975,750103.4%11,504
20041,934,63722,059,62795.7%11,402
20031,757,00919,835,05787.2%11,289
20021,796,11120,008,41889.1%11,140
20011,868,48121,528,00992.7%11,522
How these are worked out

Net generation and fuel burned are the monthly figures EIA publishes in its bulk electricity file, from the plant's Form 923 reports; a year is the sum of its months. Capacity factor is a full year's net generation over today's nameplate capacity times the hours in that year (8,784 in a leap year), so a plant uprated or partly retired since reads against its current size; heat rate is fuel burned over net generation, for plants that burn fuel. A year with fewer than twelve months stated has no capacity factor, and a value outside the plausible range is left blank rather than shown. By month, the charts apply the same rules to each month's own hours and fuel.

Sources

3 sources

Sources EIA-860M · GEM · EIA

Sources

  • EIA-860MOpen license · retrieved Nov 4, 2026
  • GEMOpen license, with credit · retrieved Oct 26, 2026Global Integrated Power Tracker, Global Energy Monitor, September 2026 release (https://globalenergymonitor.org/projects/global-integrated-power-tracker), CC BY 4.0. Modified by Inframation: TransitionZero-sourced rows removed; statuses and technologies mapped to Inframation's vocabulary; figures aggregated. Copyright © Global Energy Monitor. Global Integrated Power Tracker, September 2026 release. Distributed under a Creative Commons Attribution 4.0 International License.
  • EIAOpen license · retrieved Nov 1, 2026Source: U.S. Energy Information Administration, Electricity bulk data (Form EIA-923 monthly plant series)

Every source and license · Attribution

View at source