Show on map
Springerville — Power plant · Coal · Tucson Electric Power Co
  • Combustion
  • Operating
  • 10 · 100 · 1,000 MW

Springerville

Power plant · Coal

Key facts

Power plant · Coalran 36% of 2025 Operating
Capacity
Capacity: sourceEIA-860M · Open licenseMW
Commissioned
1985
Net generation, 2025
5,549,274 MWh
Grid
345 kV to Tucson Electric Power Co (TEPC)
Location
Apache County, Arizona

Operations

Net generation, 2025
5,549,274MWh
Fuel burned, 2025
62,787,778MMBtu
Capacity factor, 2025
35.6%
Heat rate, 2025
11,315Btu/kWh
Capacity factor % of full output, by year
Heat rate Btu per kWh, by year
Net generation, fuel burned, capacity factor and heat rate by year, newest first, as EIA's bulk electricity file states them.
YearNet generation (MWh)Fuel burned (MMBtu)Capacity factorHeat rate (Btu/kWh)
2026 (8 of 12 months)3,254,31137,162,720—11,420
20255,549,27462,787,77835.6%11,315
20245,632,01162,171,81536.0%11,039
20236,733,67074,232,88043.2%11,024
20227,144,46877,236,32245.8%10,811
20218,143,64087,404,01052.2%10,733
20207,556,12081,008,08248.4%10,721
20197,945,33484,181,30351.0%10,595
20189,961,840102,624,94563.9%10,302
20178,635,91588,325,00055.4%10,228
20169,147,05994,662,02158.5%10,349
201510,061,864104,518,76564.6%10,388
201410,539,848107,059,26667.6%10,158
201311,458,385117,690,71273.5%10,271
201210,157,288103,216,42665.0%10,162
201111,377,951118,180,36473.0%10,387
201011,129,391115,466,12771.4%10,375
20098,480,92287,686,63954.4%10,339
20088,871,87390,599,70156.8%10,212
20075,912,10761,917,30837.9%10,473
20065,801,43160,776,25037.2%10,476
20055,577,37357,400,78735.8%10,292
20045,705,73559,484,10036.5%10,425
20035,952,16161,506,92338.2%10,334
20025,830,54260,523,72437.4%10,380
20015,970,75060,523,08638.3%10,137
How these are worked out

Net generation and fuel burned are the monthly figures EIA publishes in its bulk electricity file, from the plant's Form 923 reports; a year is the sum of its months. Capacity factor is a full year's net generation over today's nameplate capacity times the hours in that year (8,784 in a leap year), so a plant uprated or partly retired since reads against its current size; heat rate is fuel burned over net generation, for plants that burn fuel. A year with fewer than twelve months stated has no capacity factor, and a value outside the plausible range is left blank rather than shown. By month, the charts apply the same rules to each month's own hours and fuel.

Sources

3 sources

Sources EIA-860M · GEM · EIA

Sources

Every source and license · Attribution

View at source